Gordon Cleanroom products LR-15 ceiling system is designed primarily for use in
pharmaceutical, hospital and food service cleanroom applications. Extruded aluminum
grid members have a ¼” upturned flange to provide a cleanable edge that also conceals
the gasket. Blank panels, filters or other ceiling components first contact the
gasket to create an airtight seal prior to settling on the tee flange.
Grid components
are fabricated of extruded aluminum for maximum structural integrity
and corrosion resistance, even in harsh environments. Aluminum assembly clips simplify
installation and require no special tools to attach grid components.
Optional hold-down clips are available to secure blank panels in the grid.
TECHNICAL INFORMATION
FINISHES
- Clear satin anodized for harsh environments
- White, water-based acrylic "wet coat" paint finish
FACTORY APPLIED GASKETS
- Closed-cell PVC, 8# density
- U.S.D.A. approved
- Fungus-resistant (Method 508.1 Mil Std 810-C)
- Flame-resistant (FMYSS #302; burn rate 4" per minute)
- Color: Light grey
- Contact factory for custom gasket availability
GRID LAYOUT MODULES
- 2' x 4'
- 2' x 2'
- Metric or custom module sizes can be provided
LR APPLICATION GUIDELINES
Appropriate for cleanrooms designed to:
- ISO-7 (Class 10,000) or higher
- Use ducted terminal filter modules
- Use cleanroom standard size filters and light fixtures
SUSPENSION AND LOAD DATA
- Minimum 12 gauge hanger wire (furnished by others)
- Hanger Wire Spacing:
- 4' o.c. for panels up to 5 lbs. per square foot
- At all 4 corners of filter
module and light fixture location
- Load test recommendations: See Table
- NOTE: Gordon does not recommend grid systems for use with fan powered modules
(FFU's). Consider Gordon rod-suspended grid systems for FFU applications.
LR PARTS
PART
NUMBER |
DESCRIPTION
 |
A-
WEB
DEPTH |
B-
EXPOSED
GASKETED
FLANGE |
PART
LENGTH |
PIECES
PER
CARTON |
LINEAL
FEET
PER
CARTON |
LBS
PER
CARTON |
WEIGHT
PER
LINEAR
FOOT/W
GASKET |
|
LR-15 |
|
LR-15-MT4 |
Main Tee,
Notched 48" o.c. |
1-1/2" |
1-1/2" |
12' |
16 |
192 |
55 |
0.31 |
|
LR-15-MT2 |
Main Tee,
Notched 24" o.c. |
1-1/2" |
1-1/2" |
12' |
16 |
192 |
55 |
0.31 |
|
LR-15-48CN |
4' Cross Tee,
Notched 24" o.c. |
1-1/2" |
1-1/2" |
4' |
48 |
192 |
54 |
0.31 |
|
LR-15-48NN |
4' Cross Tee,
No Notch |
1-1/2" |
1-1/2" |
4' |
48 |
192 |
54 |
0.31 |
|
LR-15-24 |
2' Cross Tee |
1-1/2" |
1-1/2" |
2' |
48 |
96 |
27 |
0.31 |
|
WALL ANGLES |
|
LR-WA-48 |
Wall Angle,
Notched 48" o.c. |
1-1/2" |
3/4" |
12' |
24 |
288 |
54 |
0.23 |
|
LR-WA-24 |
Wall Angle,
Notched 24" o.c. |
1-1/2" |
3/4" |
12' |
24 |
288 |
54 |
0.23 |
|
CLIPS |
|
MTS |
Main Tee Splice Clip |
One Per Main Tee |
0.02 |
|
LR-2 WAY |
2-Way Clip |
One Per LG Cross Tee |
0.01 |
|
LR-1 WAY |
1-Way Clip |
As Required |
0.01 |
|
LRHC |
Panel Hold-down Clip |
As Required |
0.01 |
|
LRHGR |
LR Hanger Clip |
As Required |
0.01 |
GREEN BY DESIGN
- LEED® 1 credits available
- 66% recycled aluminum
- 33% pre-consumer content
- 33% post consumer content
- Finishes
- No hazardous waste
- No VIC's
- No heavy metals
1 LEED® is a registered trademark of the U.S. Green Building Council.
LR COMPONENTS & ACCESSORIES
Load test recommendations outlined in the table at right should not be exceeded,
not should the components be deflected more than 1/360th of their span.
A minimum of 12 gauge hanger wire should support all four corners of the filter
unit or light fixture.
SYSTEM
TYPE |
WEB
HEIGHT |
SPAN HANGER
WIRE SPACING |
SPACING OF
MAIN TEES |
APPLIED LOAD
LBS. / SQ.FT. |
|
LR-15 |
1-3/4"" |
48"
|
24"
48" |
8.9
4.4 |